ProSoft Technology 5204-DFNT-PDPMV1 User Manual
Page 68
Configuration
PDPMV1 ♦ ProLinx Gateway
Protocol Manual
PROFIBUS DPV1 Master
Page 68 of 157
ProSoft Technology, Inc.
March 23, 2011
Parameter Data Structure
SPC3 evaluates the first seven data bytes (without user prm data), or the first
eight data bytes (with user prm data). The first seven bytes are specified
according to the standard. The eighth byte is used for SPC3-specific
communications. The additional bytes are available to the application.
Byte
Bit Position
Designation
7
6
5
4
3
2
1
0
0
Lock
Reg
Unio
Req
Sync
Req
Free
Req
WD on
Res
Res
Res
Station status
1
WD_Fact_1
2
WD_Fact_2
3
MinTSDR
4
Ident_Number_High
5
Ident_Number_Low
6
Group_Ident
7
Spec_User_Prm_Byte
8 to 243
User_Prm_Data
Byte 7
Spec_User_Prm_Byte
Bit
Name
Significance
Default State
0
Dis_Startbit
The start bit monitoring in the receiver
is switched off with this bit
Dis_Startbit = 1,
Start bit monitoring is switched off.
1
Dis_Stopbit
Stop bit monitoring in the receiver is
switched off with this bit
Dis_Stopbit = 0
Stop bit monitoring is not switched off.
2
WD_Base
This bit specifies the time base used to
clock the watchdog.
WD_Base = 0: time base 10 ms
WD_Base = 1: time base 1 ms
WD_Base = 0
The time base is 10 ms.
3 to 4
Res
To be parameterized with 0
0
5
Publisher_Enable
DXB-publisher-functionality of the
SPC3 is activated with this bit
Publisher_Enable = 0, DXB-request-
telegrams are ignored;
Publisher_Enable = 1, DXB-request-
telegrams are processed
6 to 7
Res
To be parameterized with 0
0