3.3.2 Return Codes
Possible error codes in Message Data word "Return Code" (The Return Codes
can be byte swapped)
Return Code Name
Meaning
8010h
DPMC_ERR_V1C_CLOSED
Internal DPMC instance no longer exists
8011h
DPMC_ERR_V1C_STOPPED
Internal DPMC instance has already been stopped
8012h
DPMC_ERR_V1C_STARTED
Internal DPMC instance has already been started
8013h
DPMC_ERR_V1C_STATE_UNKNOWN
Internal DPMC instance has entered an undefined
state
8021h
DPMC_ERR_V1C_REQ_ACTIVE
A request is already active
8022h
DPMC_ERR_V1C_NOT_ALLOWED
Internal DPMC module not initialized correctly
8023h
DPMC_ERR_V1C_INVALID_PAR
Invalid parameter in user request
8024h
DPMC_ERR_V1C_MEM_ALLOC
Internal memory allocation error
8025h
DPMC_ERR_V1C_L2_REQ
Unknown opcode in the confirmation
8026h
DPMC_ERR_V1C_TIMEOUT
Active request terminated with timeout
8028h
DPMC_ERR_V1C_INVALID_LEN
Invalid length in user request
8030h
DPMC_ERR_V1C_REQ_NEG
1
Negative indication from lower layer
8031h
DPMC_ERR_V1C_REQ_RE
Message frame format error in response
8042h
DPMC_ERR_V1C_REQ_WITHDRAW
Request was recalled
8043h
DPMC_ERR_V1C_REQ_NOT_FOUND
Associated request block not found
80C1h
DPMC_ERR_V1C_MM_FE
Format error in request frame
80C2h
DPMC_ERR_V1C_MM_NI
Function not implemented
80C3h
DPMC_ERR_V1C_MM_AD
Access denied
80C4h
DPMC_ERR_V1C_MM_EA
Area too large
80C5h
DPMC_ERR_V1C_MM_LE
Data block length too large
80C6h
DPMC_ERR_V1C_MM_RE
Format error in response frame
80C7h
DPMC_ERR_V1C_MM_IP
Invalid parameter
80C8h
DPMC_ERR_V1C_MM_SC
Sequence conflict
80C9h
DPMC_ERR_V1C_MM_SE
Sequence error
80CAh
DPMC_ERR_V1C_MM_NE
Area non-existent
80CBh
DPMC_ERR_V1C_MM_DI
Data incomplete or incorrect
80CCh
DPMC_ERR_V1C_MM_NC
Master parameter set not compatible
Refer to Error Codes (page 101).