Mailbox Messaging

PDPMV1 ♦ ProLinx Gateway

Protocol Manual

PROFIBUS DPV1 Master

Page 82 of 157

ProSoft Technology, Inc.

March 23, 2011

Group Select
Range 01h to FFh (Bit Coded)
This parameter determines which group to address. Refer to the following
example:

b7

b6

b5

b4

b3

b2

b1

b0

Group 8

Group 7

Group 6

Group 5

Group 4

Group 3

Group 2

Group 1


Example: To address Group 1, 2, and 4, the Group Select value should be D0h.
If an individual slave should be addressed, the correct group selection must also
be made, because the slave will ignore the message if it does not belong to the
requested group(s).
What group(s) a slave belongs to is determined during network configuration,
and is downloaded during initialization to each slave via the PROFIBUS telegram
"Set_Prm".

Control Command
This parameter specifies the command to send:

Bit

Explanation

0 (LSB)

Reserved, set to zero

1

Reserved, set to zero

2

Unfreeze input data

3

Freeze input data

4

Unsynchronize output data

5

Synchronize output data

6

Reserved, set to zero

7 (MSB)

Reserved, set to zero

Combinations of the bits (Unsync/Sync and Unfreeze/Freeze)

Bits 0 or 6

Bits 1 or 7

Explanation

0

0

No Function

0

1

Function will be activated

1

0

Function will be inactive

1

1

Function will be inactive