beautypg.com

ProSoft Technology 5204-DFNT-PDPMV1 User Manual

Page 79

background image

PDPMV1 ♦ ProLinx Gateway

Mailbox Messaging

PROFIBUS DPV1 Master

Protocol Manual

ProSoft Technology, Inc.

Page 79 of 157

March 23, 2011

Command and Response Layout: Set Operating Mode

Command

Response

Message ID

(ID)

(ID)

Acyclic Message Status

Word

4002h

0002h

Command

0002h

0002h

Set Operation Mode

Data size

0000h

0000h

Frame count

0001h

0001h

Frame number

0001h

0001h

Offset high

0000h

0000h

Offset low

0000h

0000h

Extended word 1

Mode

Conf. Req

Mode

Conf. Req

Extended word 2

-

-

Extended word 3

-

-

Extended word 4

-

-

Extended word 5

-

-

Extended word 6

-

-

Extended word 7

-

Appl. Specific Error Code

Extended word 8

-

Fault Information

Mode
40h: STOP
80h: CLEAR
C0h: OPERATE

Conf. Req.
00h: Confirmation is not required
01h: Confirmation required. All confirmations are automatically sent by the
Master; the user is not required to send a confirmation message.

Fault Information
If "Invalid Other" is returned in the Acyclic Message Status Word in the header of
the response, information about the fault can be found here. Refer to Return
Codes (page 100) for more information.
0100h: Invalid operating mode