beautypg.com

ProSoft Technology 5204-DFNT-PDPMV1 User Manual

Page 12

background image

Functional Overview

PDPMV1 ♦ ProLinx Gateway

Protocol Manual

PROFIBUS DPV1 Master

Page 12 of 157

ProSoft Technology, Inc.

March 23, 2011

1.3

PROFIBUS DP Architecture

The PROFIBUS DP-V1 Master network supports multiple Master systems with
several slaves.
The following table shows the most important features of PROFIBUS DP-V1
Master:

Standard

EIN 501 70
DIN 19245

Transmission equipment (Physical) EIA RS-485

IEC 1158-2 (through link or coupler)
Fiber Optic Cable (not available)

Transfer procedure

Half-duplex

Bus topology

Linear bus with active bus termination

Bus cable type

Shielded twisted pair conductors

Connector

9-pin D-Sub

Number of nodes on the bus

Max: 32 with no repeaters
Max: 125 with 3 repeaters in 4 segments

1.3.1 How Cable Length Affects Communication Rate

Max Bus Cable Length Per Segment

Baud Rates (for 12 Mbps cable)

1.2 km

9.6 kbit/sec

1.2 km

19.2 kbit/sec

1.2 km

93.75 kbit/sec

1.0 km

187.5 kbit/sec

0.5 km

500 kbit/sec

0.2 km

1.5 Mbit/sec

0.1 km

3 Mbit/sec

0.1 km

8 Mbit/sec

0.1 km

12 Mbit/sec

1.3.2 Bus Access

Two different bus access procedures handle the various communication
requirements for the PROFIBUS DP-V1 Master topology:
Token Passing
Polling

This manual is related to the following products: