4 To change the settings for the command, select the row, and then click E
DIT
R
OW
. This action opens the Edit - Row 1 dialog box.
Command Layout for Set Operating Mode
Column
Value
Description
Type
0 to 3
0
Command Disabled
1
Command Enabled, use poll interval
2
Command executed when database changes (Func 2, 3, 11, 12 or 33 only)
3
Command executed when database trigger set Not equal to 0
DB_Reg
If the count is set to 0, this is the database location for the operate mode. Place a value of
64 or 128 or 192 in parameter 1 for description.
Count
If Count is equal to 0, operate mode for command is derived from the DB_Reg in the
gateway database. If the count is not equal to 0, then the value in the Param_1 field is
used with the command.
Poll_Int
Only if type = 1
Swap
Not used
DB_Trigger
This functionality requires the type parameter to be set as Enabled With Trigger. The
command will be executed if the database value set by this parameter is nonzero. After
the command is executed this value will be automatically set to zero.
Func
2
Set Operate Mode.
Param_1
64, 128 or
192
This field is required if the count field is set to 1 and represents the new operation mode
as follows: 64=Stop, 128=Clear and 192=Operate.