Command Layout for Start/Stop Slaves
Column
Value
Description
Type
0 to 3
Type
0
Command Disabled
1
Command Enabled, use poll interval
2
Command executed when database changes
(Func 2, 3, 11, 12 or 33 only)
3
Command executed when database trigger set
Not equal to 0
DB_Reg
This is the database location where the 126 bytes of data for the message to be constructed
for the mailbox command is present.
Count
This field is not used as the message is always 63-words in length
Poll_Int
Only if type = 1
Swap
Utilized on request and response message
DB_Trigger
Used if type is 3
Func
11
12
Start Slave(s)
Stop Slave(s)
Param_1
This field contains the database address where the 63-words of response data from the
mailbox is written. Set to -1, if the data is not to be written to the database.
For this example, the command will stop and start the specified slave(s) using
Database trigger register 3199 (stop) and 3198 (start). Any nonzero value placed
in either register will trigger the command to execute. When the command has
executed, the database register will be reset to zero. Data will be read from
database register 3200 for a count of 63 words. The response will be placed at
Database address 3500 with a length of 63 words.