Features and benefits, General specifications, Hardware specifications – ProSoft Technology MVI71-DNP User Manual
Page 76

MVI71-DNP ♦ PLC Platform
Reference
DNP 3.0 Master/Slave Communication Module
Page 76 of 172
ProSoft Technology, Inc.
August 23, 2007
5.1.1 Features and Benefits
The module supports DNP Subset Level 2 features and some of the Level 3
features allowing the many SCADA and field devices supporting the DNP
protocol to be integrated into the PLC platform. The module acts as an
input/output module between the DNP network and the PLC backplane. The data
transfer from the PLC processor is asynchronous from the actions on the DNP
network. Databases are user defined and stored in the module to hold the data
required by the protocol.
5.1.2 General
Specifications
Single Slot – 1771 backplane compatible
The module is recognized as an Input/Output module and has access to
processor memory for data transfer between processor and module
Ladder Logic is used for data transfer between module and processor.
Sample ladder file included.
Configuration data obtained from configuration text file downloaded to
module. Sample configuration file included.
5.1.3 Hardware
Specifications
Specification
Description
Form Factor
Single Slot 1771 chassis compatible
BTR/BTW data transfer
Local or remote rack
Backplane current load
800 mA @ 5 V
Operating temperature
0 to 60°C (32 to 140°F)
Storage temperature
–40 to 85°C (–40 to 185°F)
Shock
30g operational
50g non-operational
Vibration
5 g from 10150 Hz
Relative humidity
5% to 95% (non-condensing)
LED Indicators
Module status
Backplane transfer status
Application status
Serial activity and error LED status
Debug/Configuration port (CFG)
CFG Port (P1)
RJ45 (DB-9M with supplied cable)
RS-232 only
Configuration Connector
RJ45 RS-232 Connector (RJ45 to DB-9 cable shipped with
unit)
Application Ports
Application Serial port (P2, P3)
(Serial Modules)
Two RJ45 RS-232/422/485 Application ports