beautypg.com

Dnp slave float inputs, Secondary port – ProSoft Technology MVI71-DNP User Manual

Page 37

background image

Installing and Configuring the Module

MVI71-DNP ♦ PLC Platform

DNP 3.0 Master/Slave Communication Module

ProSoft Technology, Inc.

Page 37 of 172

August 23, 2007

This section takes the following parameters:

Parameter
Number

Parameter Name

Parameter Description

1

Point #

This is the information object address of the point.

2

Class

Class 1 – Highest priority
Class 2 – Middle priority
Class 3 – Lowest priority
0 – Disable

3 Deadband

A range of values within which the module will avoid
generating events.

2.2.6 [DNP Slave Float Inputs]

This area overrides the Class 3 and deadband for the single float database. The
point number is not the address in the analog database, but rather the offset from
the start of the single floating-point database.

[DNP Slave Float Inputs]

# This area is to override the class (3) and deadband for the single float

# database. The point # is not the address in the analog database, but is

# the offset from the start of the single floating-point database.

#

# Point# Class Deadband

Start

0 1 100.

1 2 12.34

3 0 13.45 #Events will never be generated for this point

4 2 3000.0 #points 5 to 11=class 1, deadband = 1000.00

End

This section takes the following parameters:

Parameter
Number

Parameter Name

Parameter Description

1

Point #

This is the information object address of the point.

2

Class

Class 1 – Highest priority
Class 2 – Middle priority
Class 3 – Lowest priority
0 – Disable.

3 Deadband A range of values within which the module will avoid

generating events.

2.2.7 [Secondary

Port]

The following is an example of the [Secondary Port] section:

[Secondary Port]

Type : M #' '=Disabled, M=Master, S=Slave

Baud Rate : 19200 #Baud rate for port 110-115200

RTS On : 10 #0-65535 milliseconds before message

RTS Off : 0 #0-65535 milliseconds after message

Min Response Delay : 0 #0-65535 milliseconds before response sent from

slave