Float inputs, Plc float inputs, Counters – ProSoft Technology MVI71-DNP User Manual

Page 35: Plc counters, Binary outputs, Plc binary outputs, Analog outputs, Plc analog outputs

background image

Installing and Configuring the Module

MVI71-DNP ♦ PLC Platform

DNP 3.0 Master/Slave Communication Module

ProSoft Technology, Inc.

Page 35 of 172

August 23, 2007

Float Inputs

Float Inputs : 5 #0 to 250 points of floating-point format data

Number of floating-point input points to configure in the DNP slave device. Each
point will occupy a two-word area in the module memory.

PLC Float Inputs

PLC Float Inputs : 5 #0-250 points of floating-point format data

Number of floating-point input points configured above that are to be obtained
from the PLC.

Counters

Counters : 20 #0-250 points of counter data

Number of counter points to configure in the DNP slave device. Each point will
occupy a two word area in the module memory. This number corresponds to the
number of frozen counters. The application maps the counters to the frozen
counters directly.

PLC Counters

PLC Counters : 20 #0-250 counter points from PLC

Number of counter points configured above that are to be obtained from the
processor. All other counter points must come from the attached IED units.

Binary Outputs

Binary Outputs : 160 #0-2000 point count to hold BO data

Number of digital output points to configure in the DNP slave device. Each point
will be stored as a single bit in the module memory.

PLC Binary Outputs

PLC Binary Outputs : 160 #0-2000 BO point count from PLC

Number of digital output points configured above that are to be sent to the
processor. All other binary output points will be sent to the attached IED units.

Analog Outputs

Analog Outputs : 28 #0-500 points of analog output data

Number of analog output points to configure in the DNP slave device. Each point
will occupy a one word area in the module memory.

PLC Analog Outputs

PLC Analog Outputs : 28 #0-500 analog output points from PLC

Number of analog output points configured above that are to be sent to the
processor. All other analog output points will be sent to the attached IED units.