ProSoft Technology MVI71-DNP User Manual
Page 154

MVI71-DNP ♦ PLC Platform
Reference
DNP 3.0 Master/Slave Communication Module
Page 154 of 172
ProSoft Technology, Inc.
August 23, 2007
Object
Request
Response
Obj Var Description
Func
Codes
Qual
Codes
(hex)
Func
Codes
Qual
Codes
(hex)
Data
Size
(bits)
Notes
4
16-Bit Analog Input
Without Flag
1
06
129, 130
00, 01
16
Master will
generate and
process this
variation.
31
0
Frozen Analog Input
– All Variations
1
32-Bit Frozen
Analog Input
40
2
16-Bit Frozen
Analog Input
24
3
32-Bit Frozen
Analog Input With
Time To Freeze
88
4
16-Bit Frozen
Analog Input With
Time To Freeze
72
5
32-Bit Frozen
Analog Input
Without Flag
32
6
16-Bit Frozen
Analog Input
Without Flag
16
32 0 Analog
Change
Event – All
Variations
1 06,
07,
08
24
Master will
generate this
variation
1
32-Bit Analog
Change Event
Without Time
1
06, 07,
08
129, 130
17, 28
40
Master will
generate and
process this
variation (16 bit
data).
2
16-Bit Analog
Change Event
Without Time
1
06, 07,
08
129, 130
17, 28
24
Master will
generate and
process this
variation.
3
32-Bit Analog
Change Event With
Time
1
06, 07,
08
129, 130
17, 28
88
Master will
generate and
process this
variation (16 bit
data).
4
16-Bit Analog
Change Event With
Time
1
06, 07,
08
129, 130
17, 28
72
Master will
generate and
process this
variation.
33 0 Frozen
Analog
Event – All
Variations
1
32-Bit Frozen
Analog Event
Without Time
40