Reference MVI71-DNP

♦ PLC Platform

DNP 3.0 Master/Slave Communication Module

ProSoft Technology, Inc.

Page 131 of 172

August 23, 2007

[Section]/Item Value

Range

Description

Binary Outputs:

0 to 15360
points

Number of binary output points contained in
the IED database which are transferred from
the PLC processor and used by the attached
IED units.

Analog Outputs:

0 to 960 pointsNumber of analog output points contained in

the IED database which are transferred from
the PLC processor and used by the attached
IED units.

[Section]/Item

Description

[DNP Master Slave List]

Definition of the IED units to be interfaced
with the DNP master port if utilized

# This section stores information about each slave to be used by the master port. There must be an
# entry in this table for each node to be used in the command list. Two of the parameters in this list
are coded
# values:

# Conf Mode ==> 0=Never, 1=Sometimes and 2=Always (select 0).
# Flags is bit coded as
follows:

# Bit 0 (decimal 1) ==> Enable the
slave

# Bit 1 (decimal 2) ==> Use Unsolicited messaging with this slave
# Bit 2 (decimal 4) ==> Use delay measurement with this slave
# Bit 3 (decimal 8) ==> Auto time synchronization
enabled

#

# Node DL Conf Conf Conf App Rsp

# Address Mode Timeout Retry Timeout Flags
START

END

[Section]/Item

Description

[DNP Master Commands]

Definition of the commands to be issued to
the IED units by the DNP master port.

# This section contains the list of commands to process on the master port.
# Node addresses present in the command list must have an entry in the
# [DNP Slave List]. Commands with nodes not present in the list will not be
# executed.

# 1 2 3 4 5 6 7 8 9 10
#Flags/ Node Data Data Cmd Device Point DNP DB IED DB Poll
#Enable Address Object Variation Func Address Count Address Address interval
START

END