ProSoft Technology MVI71-DNP User Manual
Page 152

MVI71-DNP ♦ PLC Platform
Reference
DNP 3.0 Master/Slave Communication Module
Page 152 of 172
ProSoft Technology, Inc.
August 23, 2007
Object
Request
Response
Obj Var Description
Func
Codes
Qual
Codes
(hex)
Func
Codes
Qual
Codes
(hex)
Data
Size
(bits)
Notes
8
16-Bit Frozen Delta
Counter With Time
Of Freeze
72
9
32-Bit Frozen
Counter Without
Flag
1
06
129, 130
00, 01
32
Master will
generate and
process this
variation.
10
16-Bit Frozen
Counter Without
Flag
1
06
129, 130
00, 01
16
Master will
generate and
process this
variation.
11
32-Bit Frozen Delta
Counter Without
Flag
32
12
16-Bit Frozen Delta
Counter Without
Flag
16
22 0 Counter
Change
Event – All
Variations
1 06,
07,
08
Master will not
generate a
request for this
variation.
1
32-Bit Counter
Change Event
Without Time
129, 130
17, 28
40
Master will
process this
variation.
2
16-Bit Counter
Change Event
Without Time
129, 130
17, 28
24
Master will
process this
variation.
3
32-Bit Delta Counter
Change Event
Without Time
40
4
16-Bit Delta Counter
Change Event
Without Time
24
5
32-Bit Counter
Change Event With
Time
88
6
16-Bit Counter
Change Event With
Time
72
7
32-Bit Delta Counter
Change Event With
Time
88
8
16-Bit Delta Counter
Change Event With
Time
72
23 0 Frozen
Counter
Event – All
Variations