beautypg.com

ProSoft Technology MVI71-DNP User Manual

Page 152

background image

MVI71-DNP ♦ PLC Platform

Reference

DNP 3.0 Master/Slave Communication Module

Page 152 of 172

ProSoft Technology, Inc.

August 23, 2007

Object

Request

Response

Obj Var Description

Func
Codes

Qual
Codes
(hex)

Func
Codes

Qual
Codes
(hex)

Data
Size
(bits)

Notes

8

16-Bit Frozen Delta
Counter With Time
Of Freeze

72

9

32-Bit Frozen
Counter Without
Flag

1

06

129, 130

00, 01

32

Master will
generate and
process this
variation.

10

16-Bit Frozen
Counter Without
Flag

1

06

129, 130

00, 01

16

Master will
generate and
process this
variation.

11

32-Bit Frozen Delta
Counter Without
Flag

32

12

16-Bit Frozen Delta
Counter Without
Flag

16

22 0 Counter

Change

Event – All
Variations

1 06,

07,

08

Master will not
generate a
request for this
variation.

1

32-Bit Counter
Change Event
Without Time

129, 130

17, 28

40

Master will
process this
variation.

2

16-Bit Counter
Change Event
Without Time

129, 130

17, 28

24

Master will
process this
variation.

3

32-Bit Delta Counter
Change Event
Without Time

40

4

16-Bit Delta Counter
Change Event
Without Time

24

5

32-Bit Counter
Change Event With
Time

88

6

16-Bit Counter
Change Event With
Time

72

7

32-Bit Delta Counter
Change Event With
Time

88

8

16-Bit Delta Counter
Change Event With
Time

72

23 0 Frozen

Counter

Event – All
Variations