ProSoft Technology MVI71-DNP User Manual
Page 153

Reference MVI71-DNP
♦ PLC Platform
DNP 3.0 Master/Slave Communication Module
ProSoft Technology, Inc.
Page 153 of 172
August 23, 2007
Object
Request
Response
Obj Var Description
Func
Codes
Qual
Codes
(hex)
Func
Codes
Qual
Codes
(hex)
Data
Size
(bits)
Notes
1
32-Bit Frozen
Counter Event
Without Time
40
2
16-Bit Frozen
Counter Event
Without Time
24
3
32-Bit Frozen Delta
Counter Event
Without Time
40
4
16-Bit Frozen Delta
Counter Event
Without Time
24
5
32-Bit Frozen
Counter Event With
Time
88
6
16-Bit Frozen
Counter Event With
Time
72
7
32-Bit Frozen Delta
Counter Event With
Time
88
8
16-Bit Frozen Delta
Counter Event With
Time
72
30
0
Analog Input – All
Variations
1
06
16
Master will
generate this
variation.
1
32-Bit Analog Input
1
06
129, 130
00, 01
40
Master will
generate this
variation. Note:
Data returned
will only be
Least
Significant 16
bits from Slave
2
16-Bit Analog Input
1
06
129, 130
00, 01
24
Master will
generate and
process this
variation.
3
32-Bit Analog Input
Without Flag
1
06
129, 130
00, 01
32
Master will
generate this
variation. Note:
Data returned
will only be
Least
Significant 16