Internal slave id – ProSoft Technology MVI71-DNP User Manual
Page 28

MVI71-DNP ♦ PLC Platform
Installing and Configuring the Module
DNP 3.0 Master/Slave Communication Module
Page 28 of 172
ProSoft Technology, Inc.
August 23, 2007
Connect Timeout : 20000 #0-65535 milliseconds before connect timeout
First Character Delay : 1000 #0-65535 milliseconds before 1st char after connect
Redial Delay Time : 100 #0-65535 1/10 seconds min before redial attempt
Redial Random Delay : 150 #0-65535 1/10 seconds random before redial attempt
Idle Timeout : 200 #0-65535 1/10 seconds inactive timeout
Phone Number : ATDT18001234567
# Collision Avoidance parameters
Collision Avoidance : No #Use Collision Avoidance (Yes or No)
CD Idle Time : 10 #0-32000 mSec min idle time before transmit
CD Random Time : 15 #0-32000 mSec random idle time before transmit
CD Time Before Receive : 5 #0-65535 milliseconds before receive
#Default Class Settings
BI Class : 1 #Default class for binary input events
AI Class : 2 #Default class for analog input events
Float Class : 3 #Default class for float input events
Double Class : 0 #(Not Used)
# DNP specific parameters
AI Deadband : 10 #0-32767 analog deadband value for events
Float Deadband : 10.0 #Single float deadband
Double Deadband : 0 #(Not Used)
Select/Operate Arm Time: 2000 #1-65535 milliseconds arm timeout for select/op
outputs
Write Time Interval : 60 #0-1440 minutes for time sync from master
Data Link Confirm Mode : Never #DL confirm mode (N=Never,S=Sometimes,A=Always)
Data Link Confirm Tout : 1000 #1-65535 milliseconds DL confirm timeout
Data Link Max Retry : 2 #0-255 maximum DL confirm retry count
App Layer Confirm Tout : 2000 #1-65535 milliseconds App Layer confirm timeout
Unsolicited Response : No #Generate Unsolicited responses (Yes or No)
Class 1 Unsol Resp Min : 2 #1-255 min number of events before send
Class 2 Unsol Resp Min : 3 #1-255 min number of events before send
Class 3 Unsol Resp Min : 4 #1-255 min number of events before send
Unsol Resp Delay : 10000 #0-65535 milliseconds before events sent
UResp Master Address : 2 #DNP address of master to send UResp data
UResp Retry Count : 0 #0-255 Number of retries before switching ports
AI Events with time : No #timestamp AI Event data default (Yes or No)
Time Sync Before Events: No #timesync module before events gen (Yes or No)
Initialize DNP Database: No #Initialize the DNP Slave output database areas (Y/N)
Modify each parameter based on the needs of your application:
Internal Slave ID
Internal Slave ID : 6 #0-65534 slave identification code for this unit
This is the DNP address for the module. All messages with this address received
from the master will be processed by the module. This example shows the slave
identification code of 6.