beautypg.com

Internal slave id – ProSoft Technology MVI71-DNP User Manual

Page 28

background image

MVI71-DNP ♦ PLC Platform

Installing and Configuring the Module

DNP 3.0 Master/Slave Communication Module

Page 28 of 172

ProSoft Technology, Inc.

August 23, 2007

Connect Timeout : 20000 #0-65535 milliseconds before connect timeout

First Character Delay : 1000 #0-65535 milliseconds before 1st char after connect

Redial Delay Time : 100 #0-65535 1/10 seconds min before redial attempt

Redial Random Delay : 150 #0-65535 1/10 seconds random before redial attempt

Idle Timeout : 200 #0-65535 1/10 seconds inactive timeout

Phone Number : ATDT18001234567

# Collision Avoidance parameters

Collision Avoidance : No #Use Collision Avoidance (Yes or No)

CD Idle Time : 10 #0-32000 mSec min idle time before transmit

CD Random Time : 15 #0-32000 mSec random idle time before transmit

CD Time Before Receive : 5 #0-65535 milliseconds before receive

#Default Class Settings

BI Class : 1 #Default class for binary input events

AI Class : 2 #Default class for analog input events

Float Class : 3 #Default class for float input events

Double Class : 0 #(Not Used)

# DNP specific parameters

AI Deadband : 10 #0-32767 analog deadband value for events

Float Deadband : 10.0 #Single float deadband

Double Deadband : 0 #(Not Used)

Select/Operate Arm Time: 2000 #1-65535 milliseconds arm timeout for select/op

outputs

Write Time Interval : 60 #0-1440 minutes for time sync from master

Data Link Confirm Mode : Never #DL confirm mode (N=Never,S=Sometimes,A=Always)

Data Link Confirm Tout : 1000 #1-65535 milliseconds DL confirm timeout

Data Link Max Retry : 2 #0-255 maximum DL confirm retry count

App Layer Confirm Tout : 2000 #1-65535 milliseconds App Layer confirm timeout

Unsolicited Response : No #Generate Unsolicited responses (Yes or No)

Class 1 Unsol Resp Min : 2 #1-255 min number of events before send

Class 2 Unsol Resp Min : 3 #1-255 min number of events before send

Class 3 Unsol Resp Min : 4 #1-255 min number of events before send

Unsol Resp Delay : 10000 #0-65535 milliseconds before events sent

UResp Master Address : 2 #DNP address of master to send UResp data

UResp Retry Count : 0 #0-255 Number of retries before switching ports

AI Events with time : No #timestamp AI Event data default (Yes or No)

Time Sync Before Events: No #timesync module before events gen (Yes or No)

Initialize DNP Database: No #Initialize the DNP Slave output database areas (Y/N)

Modify each parameter based on the needs of your application:

Internal Slave ID

Internal Slave ID : 6 #0-65534 slave identification code for this unit

This is the DNP address for the module. All messages with this address received
from the master will be processed by the module. This example shows the slave
identification code of 6.