beautypg.com

Float outputs, Plc float outputs, Dnp slave binary inputs – ProSoft Technology MVI71-DNP User Manual

Page 36: Dnp slave analog inputs

background image

MVI71-DNP ♦ PLC Platform

Installing and Configuring the Module

DNP 3.0 Master/Slave Communication Module

Page 36 of 172

ProSoft Technology, Inc.

August 23, 2007

Float Outputs

Float Outputs : 4 #0-250 points of floating-point format data

Number of floating-point output points to configure in the DNP slave device. Each
point will occupy a two- word area in the module memory.

PLC Float Outputs

PLC Float Outputs : 4 #0-250 points of floating-point format data

Number of floating-point output points configured above that are to be sent to the
processor.

2.2.4 [DNP Slave Binary Inputs]

This section of the configuration file overrides the Class 2 binary database points.
Enter the list of points between the start and end labels:

[DNP Slave Binary Inputs]

# This area is to override the class (2) binary input database points.

#

# Point# Class

Start

# 0 1

# 1 2

# 2 3

# 3 0 #Events will never be generated for this point

End

This section takes the following parameters:

Parameter
Number

Parameter Name

Parameter Description

1

Point #

This is the information object address of the point.

2

Class

Class 1 – Highest priority
Class 2 – Middle priority
Class 3 – Lowest priority
0 – Disable.

2.2.5 [DNP

Slave Analog Inputs]

This section of the configuration file overrides the Class 3 and deadband for the
integer analog input database. The point number is the offset from the start of the
analog input database.

[DNP Slave Analog Inputs]

# This area is to override the class (3) and deadband for the integer analog

# input database. The point # is the offset from the start of the analog

# input database.

#

# Point# Class Deadband

Start

# 6 1 2000 #points 0-5=class 1, deadband = 1000

# 7 1 2000

# 8 2 1000

End