Dnp slave database, Binary inputs, Plc binary inputs – ProSoft Technology MVI71-DNP User Manual
Page 34: Analog inputs, Plc analog inputs

MVI71-DNP ♦ PLC Platform
Installing and Configuring the Module
DNP 3.0 Master/Slave Communication Module
Page 34 of 172
ProSoft Technology, Inc.
August 23, 2007
2.2.3 [DNP Slave Database]
The following shows an example [DNP Slave Database] section:
[DNP Slave Database]
Binary Inputs : 160 #0-8000 point count to hold BI data
PLC Binary Inputs : 160 #0-8000 BI point count from PLC
Analog Inputs : 10 #0-500 points of analog input data
PLC Analog Inputs : 10 #0-500 analog input points from PLC
Float Inputs : 10 #0-250 points of floating-point format data
PLC Float Inputs : 10 #0-250 points of floating-point format data
Double Inputs : 0 #(Not Used)
PLC Double Inputs : 0 #(Not Used)
Counters : 10 #0-250 points of counter data
PLC Counters : 10 #0-250 counter points from PLC
Binary Outputs : 160 #0-2000 point count to hold BO data
PLC Binary Outputs : 160 #0-2000 BO point count from PLC
Analog Outputs : 10 #0-500 points of analog output data
PLC Analog Outputs : 10 #0-500 analog output points from PLC
Float Outputs : 10 #0-250 points of floating-point format data
PLC Float Outputs : 10 #0-250 points of floating-point format data
Double Outputs : 0 #(Not Used)
PLC Double Outputs : 0 #(Not Used)
Edit each parameter as required for your application. The following topics
describe each parameter.
Binary Inputs
Binary Inputs : 160 #0-8000 point count to hold BI data
Number of digital input points to configure in the DNP slave device. Each point
will be stored as a single bit in the module memory.
PLC Binary Inputs
PLC Binary Inputs : 160 #0-8000 BI point count from PLC
Number of digital input points configured above that are to be obtained from the
processor. All other binary input points must come from the attached IED units.
Analog Inputs
Analog Inputs : 50 #0-500 points of analog input data
Number of analog input points to configure in the DNP slave device. Each point
will occupy a one word area in the module memory.
PLC Analog Inputs
PLC Analog Inputs : 50 #0-500 analog input points from PLC
Number of analog input points configured above that are to be obtained from the
processor. All other analog input points must come from the attached IED units.