Dnp slave database, Binary inputs, Plc binary inputs – ProSoft Technology MVI71-DNP User Manual

Page 34: Analog inputs, Plc analog inputs

background image

MVI71-DNP ♦ PLC Platform

Installing and Configuring the Module

DNP 3.0 Master/Slave Communication Module

Page 34 of 172

ProSoft Technology, Inc.

August 23, 2007

2.2.3 [DNP Slave Database]

The following shows an example [DNP Slave Database] section:

[DNP Slave Database]

Binary Inputs : 160 #0-8000 point count to hold BI data

PLC Binary Inputs : 160 #0-8000 BI point count from PLC

Analog Inputs : 10 #0-500 points of analog input data

PLC Analog Inputs : 10 #0-500 analog input points from PLC

Float Inputs : 10 #0-250 points of floating-point format data

PLC Float Inputs : 10 #0-250 points of floating-point format data

Double Inputs : 0 #(Not Used)

PLC Double Inputs : 0 #(Not Used)

Counters : 10 #0-250 points of counter data

PLC Counters : 10 #0-250 counter points from PLC

Binary Outputs : 160 #0-2000 point count to hold BO data

PLC Binary Outputs : 160 #0-2000 BO point count from PLC

Analog Outputs : 10 #0-500 points of analog output data

PLC Analog Outputs : 10 #0-500 analog output points from PLC

Float Outputs : 10 #0-250 points of floating-point format data

PLC Float Outputs : 10 #0-250 points of floating-point format data

Double Outputs : 0 #(Not Used)

PLC Double Outputs : 0 #(Not Used)

Edit each parameter as required for your application. The following topics
describe each parameter.

Binary Inputs

Binary Inputs : 160 #0-8000 point count to hold BI data

Number of digital input points to configure in the DNP slave device. Each point
will be stored as a single bit in the module memory.

PLC Binary Inputs

PLC Binary Inputs : 160 #0-8000 BI point count from PLC

Number of digital input points configured above that are to be obtained from the
processor. All other binary input points must come from the attached IED units.

Analog Inputs

Analog Inputs : 50 #0-500 points of analog input data

Number of analog input points to configure in the DNP slave device. Each point
will occupy a one word area in the module memory.

PLC Analog Inputs

PLC Analog Inputs : 50 #0-500 analog input points from PLC

Number of analog input points configured above that are to be obtained from the
processor. All other analog input points must come from the attached IED units.