ProSoft Technology MVI71-DNP User Manual
Page 151

Reference MVI71-DNP
♦ PLC Platform
DNP 3.0 Master/Slave Communication Module
ProSoft Technology, Inc.
Page 151 of 172
August 23, 2007
Object
Request
Response
Obj Var Description
Func
Codes
Qual
Codes
(hex)
Func
Codes
Qual
Codes
(hex)
Data
Size
(bits)
Notes
1
32-Bit Binary
Counter
129, 130
00, 01
40
Master will
process this
variation.
2
16-Bit Binary
Counter
129, 130
00, 01
24
Master will
process this
variation.
3
32-Bit Delta Counter
129, 130
00, 01
40
Master will
process this
variation.
4
16-Bit Delta Counter
129, 130
00, 01
24
Master will
process this
variation.
5
32-Bit Binary
Counter Without
Flag
1, 7, 8,
9, 10
06
129, 130
00, 01
32
Master will
generate and
process this
variation.
6
16-Bit Binary
Counter Without
Flag
1, 7, 8,
9, 10
06
129, 130
00, 01
16
Master will
generate and
process this
variation.
7
32-Bit Delta Counter
Without Flag
129, 130
00, 01
32
Master will
process this
variation.
8
16-Bit Delta Counter
Without Flag
129, 130
00, 01
16
Master will
process this
variation.
21
0
Frozen Counter – All
Variations
1
06
32
Master will
generate this
variation.
1
32-Bit Frozen
Counter
129, 130
00, 01
40
Master will
process this
variation.
2
16-Bit Frozen
Counter
129, 130
00, 01
24
Master will
process this
variation.
3
32-Bit Frozen Delta
Counter
40
4
16-Bit Frozen Delta
Counter
24
5
32-Bit Frozen
Counter With Time
Of Freeze
88
6
16-Bit Frozen
Counter With Time
Of Freeze
72
7
32-Bit Frozen Delta
Counter With Time
Of Freeze
88