beautypg.com

ProSoft Technology MVI71-DNP User Manual

Page 133

background image

Reference MVI71-DNP

♦ PLC Platform

DNP 3.0 Master/Slave Communication Module

ProSoft Technology, Inc.

Page 133 of 172

August 23, 2007

Word

Block
Offset

Variable Name

Description

11 13 DNP Slave address error

(Transport Layer Error)

This value counts the number of times the source
addresses contained in a multi-frame request
fragments do not match.

12 14 DNP Slave Binary Input

Event count

This value contains the total number of binary
input events which have occurred.

13 15 DNP Slave Binary Input

Event count in buffer

This value represents the number of binary input
events which are waiting to be sent to the master.

14 16 DNP Slave Analog Input

Event count

This value contains the total number of analog
input events which have occurred.

15 17 DNP Slave Analog Input

Event count in buffer

This value represents the number of analog input
events which are waiting to be sent to the master.

16 18 DNP Slave bad function

code error (Application
Layer Error)

This value counts the number of times a bad
function code for a selected object/variation is
received by the slave device.

17 19 DNP Slave object unknown

error (Application Layer
Error)

This value counts the number of times a request
for an unsupported object is received by the slave
device.

18 20 DNP Slave out of range

error (Application Layer
Error)

This value counts the number of times a
parameter in the qualifier, range or data field is
not valid or out of range.

19 21 DNP Slave message

overflow error (Application
Layer Error)

This value counts the number of times an
application response message from the slave is
too long to transmit.

20 22 DNP Slave multi-frame

message from DNP Master
error (Application Layer
Error)

This value counts the number of times the slave
receives a multi-frame message from the master.
The application does not support multi-frame
master messages.

21 23 Total

blocks

transferred

Total BTR/BTW or side-connect interface
transfers attempted by the module.

22 24 Successful blocks

transferred

This value represents the total number of transfer
operations between the PLC processor and
module that are successful.

23

25

Total errors in block transferTotal number of transfers that resulted in an error

condition.

24

26

Total BTR or write errors

Total number of BTR or write transfers that
resulted in an error.

25

27

Total BTW or read errors

Total number of BTW or read transfers that
resulted in an error.

26 28 Block

number

error Number of BTW requests that resulted in an

incorrect BTW identification code.

27 29 Continuous block error

counter

Count of sequential data transfer errors. When
this value exceeds that specified for the data
transfer operation, the error flag below will be set.

28 30 Reserved

Not

used

29 31 Configuration

Type This is a coded field that defines the configuration

of the module. The codes are as follows:
0=Single Slave Configuration, 1=Dual Slave
Configuration, 2=Slave/Master Configuration