ProSoft Technology MVI71-DNP User Manual

Page 129

background image

Reference MVI71-DNP

♦ PLC Platform

DNP 3.0 Master/Slave Communication Module

ProSoft Technology, Inc.

Page 129 of 172

August 23, 2007

[Section]/Item

Description

[DNP Slave Analog Inputs]

DNP database analog input override values

START

# This area is to override the class and deadband assignment for analog input database points. Enter
list of points
# between the START and END
labels.

#

# Point# Class Deadband

START

END

[Section]/Item

Description

[DNP Slave Float Inputs]

DNP database floating-point input override
values

# This area is to override the class and deadband assignment for float input database points. Enter
list of points
# between the START and END
labels.

#

# Point# Class Deadband

START

END

[Section]/Item Value

Range

Description

[Secondary Port]

Definitions for secondary port on module

Type:

M or S or
blank

This parameter defines the functionality of the
secondary port on the module.
M = emulate a DNP master port
S = back-up DNP slave port to the primary
port.
Any other value will disable the port.

Baud Rate:

Baud rate
value

Secondary DNP Port Baud Rate: 300, 600,
1200, 2400, 4800, 9600, 19200, 384 (38400)
, 576 (57600), 115 (115200)

RTS On:

0 to 65535
milliseconds

This value represents the number of 1 ms
increments to be inserted between asserting
the RTS modem line and the actual
transmission of the data.

RTS Off:

0 to 65535
milliseconds

This value represents the number of 1 ms
increments to be inserted after the last
character of data is transmitted before the
RTS modem line is dropped.