ProSoft Technology MVI71-DNP User Manual
Page 143

Reference MVI71-DNP
♦ PLC Platform
DNP 3.0 Master/Slave Communication Module
ProSoft Technology, Inc.
Page 143 of 172
August 23, 2007
Object
Request
Response
Obj Var Description
Func
Codes
Qual
Codes
(hex)
Func
Codes
Qual
Codes
(hex)
Data
Size
(bits)
Notes
2
Pattern Control
Block
88
Slave will return
Unknown Object to
this request.
3
Pattern Mask
16
Slave will return
Unknown Object to
this request.
20
0
Binary Counter –
All Variations
1, 7, 8,
9, 10
06
32
Slave will return
variation 5 data
1
32-Bit Binary
Counter
129, 130
00, 01
40
Slave will return
Unknown Object to
this request
2
16-Bit Binary
Counter
129, 130
00, 01
24
Slave will return
Unknown Object to
this request
3
32-Bit Delta
Counter
129, 130
00, 01
40
Slave will return
Unknown Object to
this request
4
16-Bit Delta
Counter
129, 130
00, 01
24
Slave will return
Unknown Object to
this request
5
32-Bit Binary
Counter Without
Flag
1, 7, 8,
9, 10
06
129, 130
00, 01
32
Slave will return this
variation
6
16-Bit Binary
Counter Without
Flag
1, 7, 8,
9, 10
06
129, 130
00, 01
16
Slave will return this
variation (counter
upper 16-bits
removed)
7
32-Bit Delta
Counter Without
Flag
129, 130
00, 01
32
Slave will return
Unknown Object to
this request
8
16-Bit Delta
Counter Without
Flag
129, 130
00, 01
16
Slave will return
Unknown Object to
this request
21
0
Frozen Counter –
All Variations
1
06
32
Slave will return
variation 9 data
1
32-Bit Frozen
Counter
129, 130
00, 01
40
Slave will return
Unknown Object to
this request
2
16-Bit Frozen
Counter
129, 130
00, 01
24
Slave will return
Unknown Object to
this request
3
32-Bit Frozen
Delta Counter
40
Slave will return
Unknown Object to
this request
4
16-Bit Frozen
Delta Counter
24
Slave will return
Unknown Object to
this request