beautypg.com

Master unit device profile object subset, 15 master unit device profile object subset – ProSoft Technology MVI71-DNP User Manual

Page 150

background image

MVI71-DNP ♦ PLC Platform

Reference

DNP 3.0 Master/Slave Communication Module

Page 150 of 172

ProSoft Technology, Inc.

August 23, 2007

5.15 Master Unit Device Profile Object Subset

Object

Request

Response

Obj Var Description

Func
Codes

Qual
Codes
(hex)

Func
Codes

Qual
Codes
(hex)

Data
Size
(bits)

Notes

1

0

Binary Input – All
Variations

1

06

1

Master will
generate this
variation.

1

Binary Input

1

06

129, 130

00, 01

1

Master will
generate and
process this
variation.

2

Binary Input with
Status

1

06

129, 130

00, 01

8

Master will
generate and
process this
variation.

2

0

Binary Input Change
– All Variations

1 06,

07,

08

56

Master will
generate this
variation.

1

Binary Input Change
Without Time

1 06,

07,

08

129, 130

17, 28

8

Master will
generate and
process this
variation.

2

Binary Input Change
With Time

1 06,

07,

08

129, 130

17, 28

56

Master will
generate and
process this
variation.

3

Binary Input Change
With Relative Time

1 06,

07,

08

129, 130

17, 28

24

Master will
generate and
process this
variation.

10

0

Binary Output – All
Variations

1

06

8

1

Binary Output

1

2

Binary Output
Status

129, 130

00, 01

8

Master does not
use this object
type and will not
generate a
message or
process this
type.

12

0

Control Block – All
Variations

88

1

Control Relay
Output Block

3, 4, 5, 6 17, 28

129

Echo of
request

88 Master

will

generate this
variation and
parse the
response.

2

Pattern Control
Block

88

3

Pattern Mask

16

20

0

Binary Counter – All
Variations

1, 7, 8,
9, 10

06

32

Master will
generate this
variation.