ProSoft Technology MVI71-DNP User Manual
Page 155

Reference MVI71-DNP
♦ PLC Platform
DNP 3.0 Master/Slave Communication Module
ProSoft Technology, Inc.
Page 155 of 172
August 23, 2007
Object
Request
Response
Obj Var Description
Func
Codes
Qual
Codes
(hex)
Func
Codes
Qual
Codes
(hex)
Data
Size
(bits)
Notes
2
16-Bit Frozen
Analog Event
Without Time
24
3
32-Bit Frozen
Analog Event With
Time
88
4
16-Bit Frozen
Analog Event With
Time
72
40 0 Analog
Output
Status – All
Variations
1
06
24
1
32-Bit Analog
Output Status
40
2
16-Bit Analog
Output Status
129, 130
00, 01
24
Master does not
use this object
type and will not
generate a
message or
process this
type.
41
0
Analog Output Block
- All Variations
24
1
32-Bit Analog
Output Block
40
2
16-Bit Analog
Output Block
3, 4, 5, 6 17, 28
129
Echo of
Request
24 Master
will
generate this
variation and
parse the
response.
50
0
Time and Date – All
Variations
48
1
Time and Date
2
07, With
Quant=1
48
Master will
generate this
variation.
2
Time and Date With
Interval
80
51
0
Time and Date CTO
– All Variations
1
Time and Date CTO
129, 130
07, With
Quant=1
48 Master
will
process this
variation.
2
Unsynchronized
Time and Date CTO
129, 130
07, With
Quant=1
48 Master
will
process this
variation.
52
0
Time Delay - All
Variations
1
Time Delay Coarse
129
07, With
Quant=1
16
Master will not
process this
variation.
2
Time Delay Fine
129
07, With
Quant=1
16
Master will not
process this
variation.