Object

Request

Response

Obj Var Description

Func
Codes

Qual
Codes
(hex)

Func
Codes

Qual
Codes
(hex)

Data
Size
(bits)

Notes

2

16-Bit Frozen
Analog Event
Without Time

24

3

32-Bit Frozen
Analog Event With
Time

88

4

16-Bit Frozen
Analog Event With
Time

72

40 0 Analog

Output

Status – All
Variations

1

06

24

1

32-Bit Analog
Output Status

40

2

16-Bit Analog
Output Status

129, 130

00, 01

24

Master does not
use this object
type and will not
generate a
message or
process this
type.

41

0

Analog Output Block
- All Variations

24

1

32-Bit Analog
Output Block

40

2

16-Bit Analog
Output Block

3, 4, 5, 6 17, 28

129

Echo of
Request

24 Master

will

generate this
variation and
parse the
response.

50

0

Time and Date – All
Variations

48

1

Time and Date

2

07, With
Quant=1

48

Master will
generate this
variation.

2

Time and Date With
Interval

80

51

0

Time and Date CTO
– All Variations

1

Time and Date CTO

129, 130

07, With
Quant=1

48 Master

will

process this
variation.

2

Unsynchronized
Time and Date CTO

129, 130

07, With
Quant=1

48 Master

will

process this
variation.

52

0

Time Delay - All
Variations

1

Time Delay Coarse

129

07, With
Quant=1

16

Master will not
process this
variation.

2

Time Delay Fine

129

07, With
Quant=1

16

Master will not
process this