Object
Request
Response
Obj Var Description
Func
Codes
Qual
Codes
(hex)
Func
Codes
Qual
Codes
(hex)
Data
Size
(bits)
Notes
6
16-Bit Counter
Change Event
With Time
72
Slave will return
Unknown Object to
this request
7
32-Bit Delta
Counter Change
Event With Time
88
Slave will return
Unknown Object to
this request
8
16-Bit Delta
Counter Change
Event With Time
72
Slave will return
Unknown Object to
this request
23 0 Frozen
Counter
Event – All
Variations
Slave will return
Unknown Object to
this request
1
32-Bit Frozen
Counter Event
Without Time
40
Slave will return
Unknown Object to
this request
2
16-Bit Frozen
Counter Event
Without Time
24
Slave will return
Unknown Object to
this request
3
32-Bit Frozen
Delta Counter
Event Without
Time
40
Slave will return
Unknown Object to
this request
4
16-Bit Frozen
Delta Counter
Event Without
Time
24
Slave will return
Unknown Object to
this request
5
32-Bit Frozen
Counter Event
With Time
88
Slave will return
Unknown Object to
this request
6
16-Bit Frozen
Counter Event
With Time
72
Slave will return
Unknown Object to
this request
7
32-Bit Frozen
Delta Counter
Event With Time
88
Slave will return
Unknown Object to
this request
8
16-Bit Frozen
Delta Counter
Event With Time
72
Slave will return
Unknown Object to
this request
30
0
Analog Input – All
Variations
1
06
16
Slave will respond
with variation 4 data
1
32-Bit Analog
Input
1
06
129, 130
00, 01
40
Slave will return this
variation (Note:
Data will only be
16-bit)
2
16-Bit Analog
Input
1
06
129, 130
00, 01
24
Slave will return this
variation