beautypg.com

KEPCO MBT Series User Manual

Page 64

background image

3-26

MBTSVC111609

Table 3-14 (MR, MGR Models) summarizes the effect of the CURRENT control adjustments for
different conditions. The first three columns reflect the status of the unit before the CURRENT
control is adjusted. The fourth column shows how the adjustment will affect the status of the
power supply. Refer to PAR.s 3.1.1 and 3.1.2 for more details regarding commanded and actual
mode of operation (either voltage or current).

The CURRENT control is not operational when the power supply is in Remote mode or when
you enter the MENU (PAR. 3.2.2), PROGRAM REV/CHG (PAR. 3.2.1.11.1) functions, or when a
program is running (PAR.s 3.2.1.11.3 and 3.2.1.11.5).

Rotating the CURRENT control clockwise increases output current/current limit; counterclock-
wise decreases output current/current limit.

Table 3-14 shows that if the output is disabled, with the power supply commanded to be in Cur-
rent mode, the CURRENT control adjusts the programmed output current; with the power sup-
ply commanded to be in Voltage mode, the CURRENT control adjusts programmed current
limit.

With the power supply commanded to be in Current mode, if the output is enabled and the value
of the load is less than the value of programmed voltage divided by programmed current
(R

L

< V

Prog

/ I

Prog

), the power supply operates in Current mode and the CURRENT control

adjusts actual output current. If the output is enabled and the value of the load is greater than or
equal to the value of programmed voltage divided by programmed current (R

L

≥ V

Prog

/ I

Prog

),

the power supply will be forced to operate in Voltage mode and the CURRENT control will
adjust actual current limit (this will not be apparent from the display indication; to see the revised
current limit it is necessary to view status by pressing SHIFT then (.) on the keypad).

If the power supply is commanded to be in Voltage mode with the load enabled and the load
permits the power supply to operate in Voltage mode, the CURRENT control adjusts the actual
current limit (this will not be apparent from the display indication; to see the revised current limit

TABLE 3-14. USING CURRENT CONTROL TO SET OUTPUT

CURRENT/CURRENT LIMIT — MODELS MR, MGR

POWER SUPPLY STATUS BEFORE CURENT CONTROL ADJUSTED

CURRENT CONTROL

ADJUSTS:

COMMANDED

MODE

OUTPUT

ENABLED/
DISABLED

ACTUAL MODE ***

(DICTATED BY LOAD)

CURRENT

DISABLED

CURRENT*****

Programmed output current

VOLTAGE

DISABLED

VOLTAGE*****

Programmed current limit

CURRENT

ENABLED

CURRENT

Actual output current

CURRENT

ENABLED

VOLTAGE ****

Actual Current limit **

VOLTAGE

ENABLED

VOLTAGE

Actual Current limit

VOLTAGE

ENABLED

CURRENT ****

Actual output current **

*

If the unit was programmed to Current mode remotely before being set to Local Mode, the unit will stay in current
mode until a Voltage Mode command is received.

**

“Overload” error message placed in error buffer (for use when operating in Remote mode).

*** Actual mode is indicated by the VOLTAGE MODE and CURRENT MODE status LED’s.
**** Condition where load forces power supply mode.
***** Forced by the power supply.