27�2 eltek central inverter – Solare Datensysteme Solar-Log User Manual
Page 96

96
Eltek
Eltek central inverter
27�2 Eltek central inverter
Easy Installation
Termination
Addressing
Interface
No
DIP switch
Yes
RS485
Select "Eltek Central" during the inverter detection
Overview
•
Integrated interface
•
Where to connect: Terminal strip inside the inverter
•
3-pin wiring
•
The communication address has to be assigned (1 - 247)
•
Installation steps
•
Switch off the inverters and Solar-Log™
•
Connect inverters to the Solar-Log™
•
Connect the inverters to each other
•
Configure the inverter's communication interface
•
Allocate communication address
Connect inverters to the Solar-Log™
The wiring is done using a
•
self-made, shielded 3 wire data cable and terminal block connector.
Procedure
1.
Connect wires as shown in the diagram below.
Solar-Log™ terminal strip connector
Inverter terminal strip
Terminal
Terminal
► 1
► X12.1 A (Data +)
► 3
► X12.3 GND
► 4
► X12.2 B (Data -)
2. If only one inverter is to be connected, it must be terminated according to the manufacturer's instruc-
tions.
3. Close the inverter cover if no other inverters are to be connected.
4. Insert the terminal block connector into the Solar-Log™ RS485 socket.
Connect the inverters to each other
The inverters are connected together using the RS485 interface. Refer to the manufacturer's inverter ma-
nual for the details on how to setup the connection.
Allocate communication address
•
Recommendation: Continuous numbering starting with 1 going to 247
•
Setting: Using the inverter operating display
•
Procedure: Start according to the inverter's instructions