Solare Datensysteme Solar-Log User Manual
Page 185

185
REFUSOL
REFUSOL
Set the following parameters on the inverter's operating display:
1.
Press "F1"
2.
Select
Numerical list
, press "ENTER".
3. Set parameter number
0407
press "ENTER"
4. Select sub parameter 0407,3, press "ENTER"
5. Enter "2"
[Communication type RS485: Solarlog], press "ENTER".31], press "ENTER".
6. Set parameter number
0420
press "ENTER"
7. Select sub parameter
0420,3,
press "ENTER"
8. Enter the numerical value
9600,
press "ENTER"
9. Using the installed DC isolating switch turn the inverters on and off briefly so that the settings are
activated.
Note
The numerical value "2" under point 5 in the settings refers to the old Solar-Log protocol
and the value "1" to the native protocol for active and reactive power control.
The value under point 8 refers to the inverter's baud rate and is 9600 for the old Solar-Log pro-
tocol and 57600 for the native protocol.
Allocate communication address
•
Recommendation: Continuous numbering starting with 1.
•
Setting: Using the inverter operating display
•
Procedure: Start according to the inverter's instructions
Note
To use active and reactive power management, all of the inverters need to be set to:
•
Protocol 1
•
57600 baud
•
Parameter 1164 = 2