Solare Datensysteme Solar-Log User Manual
Page 90
90
EHE
EHE N250k to N500k-TL
25�3 EHE N250k to N500k-TL
Easy Installation
Termination
Addressing
Interface
No
Yes
Yes
RS485
The following types are to be connected according to this diagram:
N250K, N250K-TL, N500K-TL
Overview
•
Integrated interface
•
Where to connect: Terminal strip inside the inverter
•
2-pin wiring
•
Communication address must be allocated.
•
Installation steps
•
Switch off the inverters and Solar-Log™
•
Connect inverters to the Solar-Log™
•
Connect the inverters to each other
•
Enter the communication address on the interver's display.
Every address may only be used once.
Address range 1 to 247.
Connect inverters to the Solar-Log™
The wiring is done using a
•
self-made cable connection with terminal block connector.
•
Where to connect: Terminal strip inside the inverter
Procedure
•
If you are making the cable yourself, connect the wires as shown in the following diagram:
Solar-Log™ terminal strip connector
Terminal strip inside the inverter
Terminal
Terminal
► 1 (Data+)
JX9 - A
► 4 (Data-)
JX9 - B
•
If only one inverter is to be connected, terminate it according to the manufacturer's specifications.
•
Insert the terminal block connector into the Solar-Log™ RS485 socket.
Connect the inverters to each other
•
Connect with a shielded twisted-pair cable.
•
Where to connect: Terminal strip inside the inverter