19 delta – Solare Datensysteme Solar-Log User Manual
Page 72

72
Delta
Delta (RS485)
19 Delta
19�1 Delta (RS485)
Easy Installation
Termination
Addressing
Interface
Yes
Resistor
Yes
RS485
Overview
•
Integrated interface
•
Where to connect: RJ45 socket on the outside of the inverter
•
2-pin wiring
•
Communication address must be allocated.
•
Installation steps
•
Switch off the inverters and Solar-Log™
•
Connect inverters to the Solar-Log™
•
Connect the inverters to each other
•
Allocate communication address
Connect inverters to the Solar-Log™
The wiring is done using a
•
ready-made Delta data cable (optional extra; not supplied)
or
•
self-made cable connection with RS485 data cable and terminal block connector.
Caution
Risk of damage to the unit!
The Solar-Log™ also has an RJ45 socket, which must never be connected to the RJ45
socket on the inverter.
►
Only connect inverters via the RS485/422 Solar-Log™ interface(s).
Procedure
1.
If you are making the cable yourself, connect the wires as shown in the following diagram:
Solar-Log™ terminal strip connector
RJ45 inverter
Terminal
PIN
► 1
► 7
► 4
► 6
► 4
► 8
Note
The PIN allocation has been changed with the new generation. 3 wired cabling functions
with both generations.