SolaX Power
SolaX Power X3
Connect the inverters to each other
•
Connect using a RJ45 cable.
•
Where to connect: RJ45 socket.
Procedure
1.
Insert the self-made cable with the RJ45 plug into any RJ45 socket on inverter 1. Connect the other
end to the terminal plug on the Solar-Log™.
2. Insert the RJ45 cable into the 2nd RJ45 socket on inverter 1 and into any RJ45 socket on
inverter 2.
3. Connect the other inverters to each other in the same way.
4. Insert the terminal block connector into the Solar-Log™ RS485 socket.
5. Terminate in the last inverter in accordance with the inverter instructions.
Allocate communication address
1.
Recommendation: Continuous numbering starting with 1.
Address range 1 - 247.
2. Setting: Using the inverter operating display.
3. Procedure: Start according to the inverter's instructions.