SolaX Power
SolaX Power X3
80�2 SolaX Power X3
Easy Installation
Termination
Addressing
Interface
No
Yes
Yes
RS485
The following types are to be connected according to this diagram:
ZDNY-TL10000, ZDNY-TL12000, ZDNY-TL15000, ZDNY-TL17000
Select SolaXPower X3 during the inverter detection.
Overview
•
Integrated interface.
•
2 RJ45 sockets on the outside of the inverter.
•
2-pin wiring.
•
Communication address must be allocated.
•
Installation steps
•
Switch off the inverters and Solar-Log™.
•
Connect inverters to the Solar-Log™.
•
Connect the inverters to each other
•
Allocate communication address.
Address range 1 to 247
Settings on the inverter's display according to the manufacturer's manual.
Connect inverters to the Solar-Log™�
The wiring is done using a
•
self-made, shielded 8 wire data cable and terminal block connector.
•
Where to connect: RJ45 socket on the inverter
Procedure
1.
If you make the cable yourself, connect the wires as shown in the following diagram.
Solar-Log™ terminal strip connector
RS485 inverter socket
Terminal
PIN
► 1
► Pin 4 - Data+
► 4
► Pin 5 - Data-
2. Insert the RJ45 plug into any RJ45 socket on inverter 1.
3. If only one inverter is to be connected, terminate it according to the inverter instructions.
4. Insert the terminal block connector into the Solar-Log™ RS485 socket.