Procedure
1.
Connect terminal 2 (A out) on inverter 1 to terminal 4 (A in) on inverter 2.
2. Connect terminal 1 (B out) on inverter 1 to terminal 3 (B in) on inverter 2.
3. Connect the other inverters to each other in the same way.
4. Terminate in the last inverter. Insert 120
Ω terminal resistor.
Allocate communication address
•
Recommendation: Continuous numbering starting with 1.
•
Setting: Using PC software for configuring inverters.
•
Procedure: Start according to the inverter's instructions