36 goodwe, 36�1 goodwe – Solare Datensysteme Solar-Log User Manual
Page 116

116
GoodWe
GoodWe
36 GoodWe
36�1 GoodWe
Easy Installation
Termination
Addressing
Interface
No
Yes
No
RS422
Overview
•
Integrated RS422 interface
•
8-pin cable – only on RS485/422 B connection of the Solar-Log™
•
Communication address does not have to be assigned
•
Installation steps
•
Switch off the inverters and Solar-Log™
•
Connect inverters to the Solar-Log™
•
Connect the inverters to each other
Connect inverters to the Solar-Log™
The wiring is done using a
•
partially ready-made RJ45 cable (not included)
or
•
self-made data cable with RJ45 plug and 6-pin terminal block connector
Caution
Risk of damage to the unit!
The Solar-Log™ also has an RJ45 socket, which must never be connected to the RJ45
socket on the inverter.
►
Only connect inverters via the RS485/422 Solar-Log™ interface(s).
Procedure
1.
Connect wires as shown in the diagram:
Solar-Log™ terminal strip connector
RJ45 inverter
Terminal
PIN
► 1
► 6 Data+ (RX_RS485A)
► 3
► 4 GND
► 3
► 5 GND
► 4
► 3 Data- (RX_RS485B)
► 5
► 8 Data+ (TX_RS485A)
► 6
► 7 Data- (TX_RS485B)
2. Run the wire from the Solar-Log™ to inverter 1 through the hole for the wire on the bottom of the unit.
3. In the inverter insert the RJ45 plug into the "RS-485 out" socket.
4. Insert the terminal block connector into the Solar-Log™ RS485 socket.