AROS Solar Technology
AROS Solar Technology (RS485)
8�2 AROS Solar Technology (RS485)
Easy Installation
Termination
Addressing
Interface
No
Yes
No
RS485
Select "Aros 485" during the inverter detection
Overview
•
Integrated interface
•
Where to connect: Terminal strip inside the inverter
•
3-pin wiring
•
Communication address does not have to be assigned
Note:
The order in which the inverters are displayed in the Solar-Log™ after detection is random.
We strongly recommend that you change the order of the inverters immediately after de-
tection at startup in the
Configuration | Device | Configuration | Order
menu box.
The inverters can be identified using the displayed serial number.
•
Installation steps
•
Switch off the inverters and Solar-Log™
•
Connect inverters to the Solar-Log™
•
Connect the inverters to each other
Connect inverters to the Solar-Log™
The wiring is done using a
•
self-made cable connection with terminal block connector.
Procedure
1.
If you are making the cable yourself, connect the wires as shown in the following diagram:
Solar-Log™ terminal strip connector
RJ45 inverter
Terminal
PIN
► 1
► A (+)
► 3
► GND
► 4
► B (-)
2. If only one inverter is to be connected terminate this in accordance with the inverter instructions.
3. Insert the terminal block connector into the Solar-Log™ RS485 socket.
Connect the inverters to each other
•
Connect using a 3 wire, shielded data cable
•
Where to connect: Terminal strip inside the inverter