81 solectria – Solare Datensysteme Solar-Log User Manual
Page 248

248
Solectria
Solectria >9k
81 Solectria
81�1 Solectria >9k
Easy Installation
Termination
Addressing
Interface
No
Yes
Yes
RS485
The following types are to be connected according to this diagram:
PVI 10KW
PVI 13KW
PVI 15KW
PVI 100KW
Overview
•
Integrated interface
•
Where to connect: Terminal strip inside the inverter
•
3-pin wiring
•
Communication address must be allocated.
•
Installation steps
•
Switch off the inverters and Solar-Log™
•
Connect inverters to the Solar-Log™
•
Connect the inverters to each other
•
Change the communication address if required.
Every address may only be used once.
Address range 1 to 16.
Connect inverters to the Solar-Log™
The wiring is done using a
•
self-made cable connection with terminal block connector.
•
Where to connect: Terminal strip inside the inverter
Procedure
•
If you are making the cable yourself, connect the wires as shown in the following diagram:
Solar-Log™ terminal strip connector
Terminal strip inside the inverter
Terminal
PIN
► 1 (Data+)
RS485 A
► 3 (Ground)
RS485 G
► 4 (Data-)
RS485 B
•
If only one inverter is to be connected, according to the manufacturer's handbook it must be termi-
nated.
•
Insert the terminal block connector into the Solar-Log™ RS485 socket.