Easy Installation
Termination
Addressing
Interface
No
Yes
Yes
RS485
Overview
•
Integrated interface
•
Where to connect: 9 pin socket on the outside of the housing floor.
•
2-pin wiring
•
Communication address must be allocated.
•
Installation steps
•
Switch off the inverters and Solar-Log™
•
Install the RS485 interface in the inverter
•
Connect inverters to the Solar-Log™
•
Connect the inverters to each other
•
Allocate communication address
Connect inverters to the Solar-Log™
The wiring is done using a
•
ready-made Santerno data cable (optional extra; not supplied)
or
•
self-made, shielded 2 wire data cable with a 9 pin plug and a terminal block connector.
Procedure
1.
If you are making the cable yourself, connect the wires as shown in the following diagram:
Solar-Log™ terminal strip connector
Inverter terminal strip
Terminal
Terminal
► 1
► 1 (A-Line)
► 4
► 2 (B-Line)
2. Insert the plug into socket A on the inverter.
3. If only one inverter is to be connected this must be terminated.
Connect socket A on the Santerno Solar-Log™ data cable to the plug of the first Santerno inverter data
cable.
4. Insert the terminal block connector into the Solar-Log™ RS485 socket.
Connect the inverters to each other
•
Santerno inverter data cable (optional extra; not supplied)
•
Where to connect: 9 pin socket on the outside of the housing floor.