68�2 salicru eqxlv – Solare Datensysteme Solar-Log User Manual
Page 194

194
SALICRU
SALICRU EQXLV
68�2 SALICRU EQXLV
Easy Installation
Termination
Addressing
Interface
No
Resistor
Yes
RS485
Overview
•
Integrated interface
•
2-pin wiring
•
Communication address must be allocated.
•
Installation steps
•
Switch off the inverters and Solar-Log™
•
Connect inverters to the Solar-Log™
•
Connect the inverters to each other
•
Allocate communication address
Connect inverters to the Solar-Log™
The wiring is done using a
•
ready-made data cable (optional extra; not supplied)
or
•
self-made, shielded 2 wire data cable and terminal block connector.
Procedure
1.
If you are making the cable yourself, connect the wires as shown in the following diagram:
Solar-Log™ terminal strip connector
Inverter terminal strip
Terminal
Terminal
► 1
► 4 (A in)
► 4
► 3 (B in)
2. If only one inverter is to be connected this must be terminated.
Insert 120
Ω terminal resistor.
3. Insert the terminal block connector into the Solar-Log™ RS485 socket.
Connect the inverters to each other
•
Connect using a 2 wire, shielded data cable
•
Where to connect: Terminal strip inside the inverter
Procedure
1.
Connect terminal 2 (A out) on inverter 1 to terminal 4 (A in) on inverter 2.
2. Connect terminal 1 (B out) on inverter 1 to terminal 3 (B in) on inverter 2.
3. Connect the other inverters to each other in the same way.
4. Terminate in the last inverter. Insert 120
Ω terminal resistor.
Allocate communication address
•
Recommendation: Continuous numbering starting with 1.
•
Setting: Using PC software for configuring inverters.
•
Procedure: Start according to the inverter's instructions