APPLICATIONS

2.4.2 Zero-clamp cont.

— 2-42 —

Cn-01

Setting

Control Mode

Bit B Bit A

Control Mode

Zero-clamp Speed Control
This speed control allows the
zero-clamp function to be set when
the motor stops.
D

A speed reference is input from
V-REF.

D

/P-CON is used to turn the
zero-clamp function ON or OFF.

Servopack

Speed reference

Zero-clamp

(CN1-12)

/P-CON

(CN1-1*)

0

1

/P-CON is open

(OFF)

Turns

zero-clamp

function OFF

Zero-clamp is performed when the
following two conditions are met:
/P-CON signal is closed.

/P-CON is

closed (ON)

Turns

zero-clamp

function ON

/P CON signal is closed.
Motor speed is below the value set
in Cn-0F (ZCLVL).

D

Torque reference input T-REF
cannot be used.

Settings

Set the motor speed level at which zero-clamp is to be performed in the following parameter.

Cn-0F

ZCLVL Zero-clamp

Level

Unit:

min

−1

Setting Range:

0 to Maximum

Speed

Factory

Setting:

10

For Speed/Torque

Control

If zero-clamp speed control is selected, set the motor speed level at which zero-clamp is to be
performed.

Conditions for Zero-clamp

Zero-clamp is performed when all the following conditions are met:

• Zero-clamp speed control is selected.(Bits A and B of memory switch Cn-01 are set to 1

and 0, respectively.)

• /P-CON is turned ON (0 V).

• Motor speed drops below the preset value.

Speed

V-REF speed reference

Preset value for

zero-clamp

/P-CON input

Zero-clamp being

performed

Open (OFF)

Closed (ON)

Time

2