beautypg.com

Contact closure digital input, Digital dc input – Wavetronix Click 500 (programmable controller) (CLK-500) - Developer Guide User Manual

Page 23

background image

22

CHAPTER 1 • USING THE CLICK 500

Note

Wavetronix offers a 6-foot shielded extension cable to prevent AC coupling crosstalk
when a longer cable run is necessary. If you make your own extension cable, be sure
to use shielded cable and to properly ground the shield as illustrated in the following
figure.

Solder joint for black wires

Solder joint for white

and drain wires

Heat shrink

White heat shrink

Foil shield

Jacket of 6' cable

Signal (I1+ or I2+)
Ground (I1- or I2-)

Heat shrink

Solder joint

White wire Drain wire

White heat shrink

Figure 1.10 – AC Transformer Extension Cable Diagram

Contact Closure Digital Input

If a digital input is used to monitor contact closures, connect the I1+ pin to one side of the

contact output and the I1- pin to the other side of the contact output. For demonstration

and troubleshooting purposes you can use the digital inputs to monitor the contact closure

outputs of the Click 500 itself. To do so, wire I1+ to O1+, I1- to O1-, I2+ to O2+ and I2- to

O2-.

Note

I1- and I2- are both connected to Click 500 ground. Do not apply positive voltage to
these connectors as they are intended as a ground return.

Digital DC Input

When a digital input is used to monitor DC voltage, one of the following three different

thresholds can be selected: 9, 11.6, or 23.3 VDC. If the input voltage is greater than the

selected threshold, the input is designated as being in the ON state with a logical 1; if the

input voltage is less than the selected threshold, the input is designated as being in the OFF

state with a logical 0.