beautypg.com

Using the dip switches, Program mode/run mode, Warning – Wavetronix Click 500 (programmable controller) (CLK-500) - Developer Guide User Manual

Page 18

background image

CHAPTER 1 • USING THE CLICK 500 17

Using the DIP Switches

The DIP switches on the side of the module allow you to quickly and easily put the Click 500

in program mode or run mode (see Figure 1.6).

Figure 1.6 – Photo of DIP Switches

Program Mode/Run Mode

The Click 500 will need to be in program mode whenever you are developing an applica-

tion. To do so, make sure that the 6th switch of DIP switch 1 on the side panel is in the ON

position.

When you are done developing an application, and want to deliver a device to the end user,

you will need the device to be in run mode. By putting the 6th switch of DIP switch 1 on

the side panel into the OFF position, the device will be in run mode and cannot be pro-

grammed (unless the switch is turned back on).

Warning

With older versions of the Click 500 series module, it is necessary to remove pin 4
from the serial cable to prevent the device from going into programming mode. If it
enters programming mode (and you are not using the debugger), all of the faceplate
LEDs will turn off. To exit programming mode, power will need to be cycled on the
device.

Mode

1

2

3

4

5

6

Program

On

Run

Off

Table 1.1 – Program and Run Mode DIP Switch 1 Settings