MDE-5013C TopKAT™ PLUS Installation Manual · February 2015

Page 5-3

Troubleshooting

Maintenance

Mechanic pump does not refuel

Pump does not supply fuel

Device is not allowed to
refuel

1 Open the pump from SiteOmat status

screen.

2 Ensure that the vehicle/device has no

limitation in FHO setup.

Enable the device to refuel.

Pump setup is incorrect

Check pump setup:

• Pump Server
• Buses
• Prices
• Pulse rate

1 Set pump parameters.
2 Save and reload.
3 Check again.

Faulty connection to pump

Check control cables from TopKAT PLUS
to pump.

Make good electrical connection.

8-port failure

Ensure that power LED is lit.

If it is off, use a voltmeter to check
power supply to the unit: If power
supply is OK, then replace the 8-port
board. If power supply is faulty,
replace the power supply.

Ensure that control red LED on MPI-C
board is lit.

1 Replace MPI-C board.
2 Replace 8-port.

Pump malfunction

Turn the external bypass switch on, lift the
nozzle, and check that the pump supplies
fuel.

If the problem persists:
1 Check Handle-On switch.
2 Repair pump.

Handle-on switch problem

Is the In Use red LED in MPI-C board lit
when nozzle is lifted?

1 Check in use cable and repair, if

required.

2 Check terminal wires and repair, if

required.

3 Check the in ise switch in the pump

and repair, if required.

Pump is authorized but call
state is not detected (nozzle
icon in SiteOmat status
screen does not display Call
state)

Faulty in use switch in
pump

Power off the pump using a ohmmeter,
measure the switch in on and off states.

Replace pump switch in cases where
no short was detected.

Faulty connections

Check In Use cable

Check In Use terminal block connections.

Make good electrical connection if
faulty one exists.

Faulty in use terminal block

Replace in use terminal block.

Faulty MPI-C board

Ensure that the call red LED is lit when
nozzle is lifted.

If the red LED is not lit, replace

MPI-C board. If the LED is lit, the
problem is external to the controller.

Faulty 8-port

Replace 8-port.

Pump is authorized, pump
motor is running, but no fuel
is supplied

Faulty solenoid valve

Faulty pump

Does the pump solenoid valve produce a
clicking sound?

1 Replace valve.
2 Repair pump.

Fault

Probable Cause

Checks

Corrective Action