MDE-5013C TopKAT™ PLUS Installation Manual · February 2015
Page 3-15
Mechanical Pump - Wiring
TopKAT PLUS Installation Procedures
Figure 3-12: TopKAT PLUS - Mechanical Pump Wiring List Label
Mechanical Pump - Required Connections
This paragraph describes the required wiring connections between the mechanical pump and
TopKAT PLUS.
and
show a schematic diagram of the
connections between the TopKAT PLUS and the mechanical pump components.
on
shows a detailed wiring diagram between the TopKAT PLUS terminal block and
pump components.
Pulse Input
Wires
The dispenser outputs pulses to the system by means of the pulser unit,
installed in accordance with the manufacturer instructions. The pulse rate
per volume (liter/gallon) is determined by the pulser unit. It is programmed
as a “factor” in the SiteOmat.
Handle Status
Input Wires
The handle signal is used to signal the system that the pump is “In Use”
mode. When the dispenser handle is lifted, this contact closes. This signals
the system that the pump is “In Use” or that the transaction ended.
Authorization
Output Wires
The dispenser requires an authorization signal from the TopKAT PLUS to
start a sale transaction. Without this authorization signal, the electric valve
(or pump) does not open and the sale transaction does not begin. The
TopKAT PLUS switches the AC power signal to the valve. When the
dispenser receives the authorization signal, fuel starts to flow. This signal is
also referred to as the LOAD.
TopKAT PLUS ratings for above signals are as follows:
Signal
TopKAT PLUS Rating
Pulser Input
3 mA, 15 VDC max.
Pulser Power Output 12 VDC, 30 mA max.
In Use Input
100-240 VAC, 50/60 Hz, 2 W (20 mA)
Load
3/4 HP @115 V
1.5 HP @ 240 V