CFN III Quick Reference

Page 46

MDE-4483 CFN III Quick Reference Guide v3.3 · August 2005

numeric character is incremented by one each time
the PCU reset-to-start/complete times out, until the
maximum timeout of 15 (15 is F in hexadecimal
counting) seconds is reached.
Test Mode. When test mode is activated with switch
C-8, switch C-5 determines the relay limits:

C-5

Function

open

pump slows at 500 pulses and turns off at 510
pulses

closed

pump slows at 50 pulses and turns off at 60
pulses

In test mode, switches C-6 and C-7 select the pump
to be tested:

Pump to Test

C-6

C-7

1

closed

closed

2

open

closed

3

closed

open

4

open

open

Jumpers

Jumper Setting

Setting

Default

K1

installed=battery
connected

removed=battery
disconnected

installed

CMOS CPU Board

Part number: C05321

LEDs

LED

Color

Function

L1

red

422 transmit

L2

red

422 receive

L3, 4, 5, 6

red

submersible & slow flow, pump

1, 2, 3, 4

L7, 8, 9, 10

red

fast flow, pump 1, 2, 3, 4

Switches

DIP switch banks B and C on the CMOS CPU board
set options latched in at power-up time.

DIP Switch Bank B

Position & Definition

Setting(*=customary)

1-4

address

see below

5

address

*always closed

6

address

*always closed

7

baud rate

*open=9600
closed-see below

8

baud rate

*closed=9600

open-see below

Address

B-1

B-2

B-3

B-4

B-5

B-6

1

cl

cl

cl

cl

cl

cl

2

op

cl

cl

cl

cl

cl

3

cl

op

cl

cl

cl

cl

4

op

op

cl

cl

cl

cl

5

cl

cl

op

cl

cl

cl

6

op

cl

op

cl

cl

cl

7

cl

op

op

cl

cl

cl

8

op

op

op

cl

cl

cl

9

cl

cl

cl

op

cl

cl

10

op

cl

cl

op

cl

cl

11

cl

op

cl

op

cl

cl

12

op

op

cl

op

cl

cl

13

cl

cl

op

op

cl

cl

14

op

cl

op

op

cl

cl

15

cl

op

op

op

cl

cl

16

op

op

op

op

cl

cl

Baud Rate

B-7

B-8

not used

closed

closed

9600

open

closed

1200

closed

open

300

open

open

DIP Switch Bank C

Position & Definition

Setting(*=customary)

1-4

pulser enabled
pumps 1-4

*closed=after reset is
complete
open=upon activation

5

CRC required

*open=required
closed =not required

6

dead man timer

*always open=enabled

7

____

8

test mode

*closed=no
open=yes

Jumpers

Jumper Setting-IN

Setting-OUT

Default

K1

normal

battery test

installed

K2

battery

no battery

installed