Echelon LNS User Manual
Page 217
LNS Programmer's Guide
203
Table 9.2 NvMonitorOptions Object
Property Name
Description
Authentication
This property is not used. If the UseBoundUpdates
option for a monitor point is set to True, the monitor
point’s authentication state is determined by the
UseAuthenticationFlag property of the
ConnectDescTemplate specified when the monitor
point was created. Otherwise, the authentication state is
set based on the monitored network variable’s current
authentication state.
GenerateInitialFetch
This property determines whether the values of the
network variable monitor points in the monitor set will
be fetched when the monitor set is enabled (
True
). If this
property is set to
False
, the value of each network
variable monitor point in the set will not be updated
until a network variable update for that point is received
due to an explicit fetch, bound update, or expired poll
interval.
Default Value: False
PollInterval
This property determines the interval to use when
polling the network variables being monitored by this
set.
Default Value: 1000 ms*
*The default value for this property for temporary
monitor sets is set to match the value of the
DsPollInterval property.