beautypg.com

8list of the modbus variables – EVCO c-pro nano RACK User Manual

Page 73

background image

C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL

Page 73

8

List of the MODBUS variables


It is possible to check the application through a supervisor, using the Modbus protocol. The communication
occurs through a serial TTL interface, which is already integrated in the controller; we suggest using the
external TTL/RS-485 interface (the interface is not supplied with the instrument).
The various parameters that are exported by the application in the three versions of the application are reported
below.

Modbus Table

REGISTER VARS LIST

Id

Name

Value

Min

Max

Description

Mode

257

PackedDI

0

0

65535

bit00=DI01,
bit01=DI02,
bit02=DI03,
bit03=DI04,
bit04=DI05,
bit05=DI06,
bit06=DI07,
bit07=DI08,
bit08=DI09,
bit09=DI10,
bit10=free,
bit11=free,
bit12=free,
bit13=free,
bit14=free,
bit15=free

R/W

385

PackedDO

0

0

65535

bit00=DO01,
bit01=DO02,
bit02=DO03,
bit03=DO04,
bit04=DO05,
bit05=DO06,
bit06=DO07,
bit07=DO08,
bit08=DO09,
bit09=DO10,
bit10=DO11,
bit11=DO12,
bit12=free,
bit13=free,
bit14=free,
bit15=free

R/W

513

AI_Pressure_SuctionC1

-

-

-

Bar

R/W

514

AI_Pressure_SupplyC1

-

-

-

Bar

R/W

515

AI_Pressure_SuctionC2

-

-

-

Bar

R/W

516

AI_Pressure_SupplyC2

-

-

-

Bar

R/W

517

AI_EnvironmentProbe

-

-

-

_C

R/W

518

AI_ExternalProbe

-

-

-

_C

R/W

641

CmpInverter_Circuit1

0.00

0.00

100.00

%

R/W

642

FanInverter_Circuit1

0.00

0.00

100.00

%

R/W

643

CmpInverter_Circuit2

0.00

0.00

100.00

%

R/W

644

FanInverter_Circuit2

0.00

0.00

100.00

%

R/W

769

PackedAlarm1

0

0

65535

bit00=EN01,
bit01=ES01,
bit02=ES02,
bit03=ES03,
bit04=ES04,
bit05=free,

R/W