C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL

Page 40

PA17

Set the setpoint for high pressure alarm over
suction probe of circuit 1

4.0

PA15

PH02

Bar

IS-S

PA18

Set the differntial for high pressure alarm
over suction probe of circuit 1

0.5

0.0

20.0

Bar

IS-S

PA19

Set the setpoint for low pressure alarm over
discharging probe of circuit 1

2.0

PH03

PA21

Bar

IS-S

PA20

Set the differntial for low pressure alarm
over discharging probe of circuit 1

0.5

0.0

20.0

Bar

IS-S

PA21

Set the setpoint for high pressure alarm over
discharging probe of circuit 1

20.0

PA19

PH04

Bar

IS-S

PA22

Set the differntial for high pressure alarm
over discharging probe of circuit 1

1.0

0.0

20.0

Bar

IS-S

PA23

Set the rearmament type for fan’s thermal
alarm

M

A (0)

M (1)

-

IS-S

PA25

Set the setpoint for low pressure alarm over
suction probe of circuit 2

0.5

PH01

PA27

Bar

IS-S

Visible if

PG01 > 1

PA26

Set the differntial for low pressure alarm
over suction probe of circuit 2

0.5

0.0

20.0

Bar

IS-S

Visible if

PG01 > 1

PA27

Set the setpoint for high pressure alarm over
suction probe of circuit 2

4.0

PA25

PH02

Bar

IS-S

Visible if

PG01 > 1

PA28

Set the differntial for high pressure alarm
over suction probe of circuit 2

0.5

0.0

20.0

Bar

IS-S

Visible if

PG01 > 1

PA29

Set the setpoint for low pressure alarm over
discharging probe of circuit 2

2.0

PH03

PA31

Bar

IS-S

Visible if

PG01 > 1

and

PG30 = 0

PA30

Set the differntial for high pressure alarm
over discharging probe of circuit 2

0.5

0.0

20.0

Bar

IS-S

Visible if

PG01 > 1

and

PG30 = 0

PA31

Set the setpoint for high pressure alarm over
discharging probe of circuit 2

20.0

PA29

PH04

Bar

IS-S

Visible if

PG01 > 1

and

PG30 = 0

PA32

Set the differntial for high pressure alarm
over discharging probe of circuit 2

1.0

0.0

20.0

Bar

IS-S

Visible if

PG01 > 1

and

PG30 = 0

PSd3

Set the password of Installer level

0

-999

9999

n

IS-V

PG01

Set the number of circuits of the machine

1

1

2

n

CO-W

PG02

Enable the presence of the expansion

0 = No

No (0)

Si (1)

-

CO-W

PG03

Enable the management of different
compressors with different power

0 = No

No (0)

Si (1)

-

CO-W

PG04

Set the number of throttlings for each
compressor

0

0

2

n

CO-W

PG05

Set the thermal security of the compressors

1 = Si

0

1

-

CO-W

PG11

Set the number of compressors of circuit 1

2

0

4

n

CO-W

PG12

Enable the inverter of compressors of circuit
1

0 = No

No (0)

Si (1)

-

CO-W

PG15

Set the number of compressors of circuit 2

0

0

4

n

CO-W

Visible if

PG01 > 1

PG16

Enable the inverter of compressors of circuit
2

0 = No

No (0)

Si (1)

-

CO-W

Visible if

PG01 > 1

PG30

Set the singular condensation for the group
of the fans

0 = No

0

1

-

CO-W

PG32

Enable the thermal security of the fans

1 = Si

0

1

-

CO-W

PG41

Set the number of fans of circuit 1

2

0

4

n

CO-W

PG42

Enable the fans' inverter of circuit 1

0 = No

No (0)

Si (1)

-

CO-W

PG45

Set the number of fans of circuit 2

0

0

4

n

CO-W

Visible if

PG01 > 1

and

PG30 = 0