C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL

Page 32

5.1

Parameters configuration list

Code

Parameter description

Default

Min

Max

U.M.

Menu

Notes

SPC1

Set the setpoint value for the suction probe
of the compressors (circuit 1)

1.0

PC12

PC13

Bar

UT-C1

PUC1

Set the offset value by digital input for the
use of compressors’ secondary setpoint
(circuit 1)

0.0

-20.0

20.0

Bar

UT-C1

PUC4

Ses the offset value by supervision for the
use of compressors’ secondary setpoint
(circuit 1)

0.0

-20.0

20.0

Bar

UT-C1

SPF1

Set the setpoint value for the discharging
probe of the fans (circuit 1)

15

PF12

PF13

Bar

UT-C1

PUF1

It sets the offset value from digital input for
the use of fans’ secondary setpoint (circuit
1)

0.0

-20.0

20.0

Bar

UT-C1

PUF4

Set the offset value by supervision for the
use of fans’ secondary setpoint (circuit 1)

0.0

-20.0

20.0

Bar

UT-C1

SPC2

Set the setpoint value for the suction probe
of the compressors (circuit 2)

1.0

PC32

PC33

Bar

UT-C2

Visibile if

PG01 > 1

PUC2

Set the offset value by digital input for the
use of compressors’ secondary setpoint
(circuit 2)

0.0

-20.0

20.0

Bar

UT-C2

Visibile if

PG01 > 1

PUC5

Set the offset value by digital input for the
use of compressors’ secondary setpoint
(circuit 2)

0.0

-20.0

20.0

Bar

UT-C2

Visibile if

PG01 > 1

SPF2

Set the setpoint value for the discharging
probe of the fans (circuit 2)

15

PF32

PF33

Bar

UT-C2

Visibile if

PG01 > 1

PUF2

Set the offset value by digital input for the
use of fans’ secondary setpoint (circuit 2)

0.0

-20.0

20.0

Bar

UT-C2

Visibile if

PG01 > 1

PUF5

Set the offset value by digital input for the
use of fans’ secondary setpoint (circuit 2)

0.0

-20.0

20.0

Bar

UT-C2

Visibile if

PG01 > 1

PSd1

Modify the password on User level

0

-999

9999

UT

PM00

Set in tens the maximum limit of
compressors’ operation hours. Beyond this
limit the respective alarm will go off.

2000

0

9999

hours

x

10

MA-F

PM01 ..
.. PM04

Represent in tens the compressors’
operation hours. One for each compressor.

0

0

9999

hours

x

10

MA-F

Visibility

*1

PM40

Set in tens the maximum limit of fans’
operation hours. Beyond this limit the
respective alarm will go off.

2000

0

9999

hours

x

10

MA-F

PM41 ..
.. PM44

Represent in tens the fans’ operation hours.
One for each fan

0

0

9999

hours

x

10

MA-F

Visibility

*2

PM91

Set the last date when plant’s maintenance
has been done

2006

2000

2064

n

MA-F

PM92

Set the last date when plant’s maintenance
has been done

1

1

12

n

MA-F

PM93

Set the last date when plant’s maintenance
has been done

1

1

31

n

MA-F

PM11 ..
.. PM14

Enable the compressor’s manual/automatic
operation:
Manu: manual
Auto: normal function
One for each compressor

Auto

Auto (0)

Manu

(1)

-

MA-M

Visibility

*1

PM21 ..
.. PM24

If it is in manual function, it sets the number
of steps to be forced to the compressor
One for each compressor

0

0

3

n

MA-M

Visibility

*1

PM37

If it is in manual function, it forces the
compressors’ inverter value of circuit 1

0

0

100.0

%

MA-M

Visibile if

PG12 = 1

PM38

If it is in manual operation, it forces the

0

0

100.0

%

MA-M

Visibile if