C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
Page 41
PG46
Enable the inverter of fans of circuit 2
0 = No
No (0)
Si (1)
-
CO-W
Visible if
PG01 > 1
and
PG30 = 0
HC01
Set the digital output position for
compressor 1
Or
Set the inverter compressor consent position
for circuit 1 (if circuit 1 inverter is enabled)
1
0
14
n
CO-Hw
HC02
Set the digital output position for
compressor 2
Or
Set the inverter compressor consent position
for circuit 2 (if circuit 2 inverter is enabled)
2
0
6 (12)
n
CO-Hw
HC03
Set the digital output position for
compressor 3
Or
Set the inverter compressor consent position
for circuit 3 (if circuit 3 inverter is enabled)
0
0
6 (12)
n
CO-Hw
HC04
Set the digital output position for
compressor 4
Or
Set the inverter compressor consent position
for circuit 4 (if circuit 4 inverter is enabled)
0
0
6 (12)
n
CO-Hw
(13)
PWM1
Consent
(14)
PWM2
Consent
Visibility
*¹
HC11
Set the digital output position for the
throttling 1 of compr.1
0
0
6 (12)
n
CO-Hw
(12 if
expansion
is
enabled);
visibility
*1
HC12
Set the digital output position for the
throttling 1 of compr. 2
0
0
6 (12)
n
CO-Hw
(12 if
expansion
is
enabled);
visibility
*1
HC13
Set the digital output position for the
throttling 1 of compr.3
0
0
6 (12)
n
CO-Hw
(12 if
expansion
is
enabled);
visibility
*1
HC14
Set the digital output position for the
throttling 1 of compr.4
0
0
6 (12)
n
CO-Hw
(12 if
expansion
is
enabled);
visibility
*1
HC21
Set the digital output position for the
throttling 2 of compr.1
0
0
6 (12)
n
CO-Hw
(12 if
expansion
is
enabled);
visibility
*1
HC22
Set the digital output position for the
throttling 2 of compr.2
0
0
6 (12)
n
CO-Hw
(12 if
expansion
enabled);
visibility
*1
HC23
Set the digital output position for the
throttling 2 of compr.3
0
0
6 (12)
n
CO-Hw
(12 if
expansion
is
enabled);