EVCO c-pro nano RACK User Manual
Page 71

C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
Page 71
AL32
High discharge pressure C2
Auto
ON all fans
AL37
High suction pressure C2
Auto
ON all comp.
Delay able to be set
AL42
Low discharge pressure C2
Auto
OFF all fans
Delay able to be set
AL47
Low suction pressure C2
Auto
OFF all comp.
Delay able to be set
AL12
High discharge pressure pressure regulator C2
Set
OFF all com.
AL22
Low suction pressure pressure regulator C2
Auto
OFF all comp.
AL62
Liquid level C2
Manu
Visualization
Delay able to be set
ACC2
Common oil differential C2
Set
Visualization
Delay able to be set
AFC2
Common thermal fans C2
Set
Visualization
ES07
Environment probe broken or disconnected
Auto
Visualization
ES08
External probe broken or disconnected
Auto
Visualization
AH01
Hardware configuration alarm
Auto
Visualization
(*) The low-pressure alarms are not active when the machine is off, while all the others are.