C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL

Page 71

AL32

High discharge pressure C2

Auto

ON all fans

AL37

High suction pressure C2

Auto

ON all comp.

Delay able to be set

AL42

Low discharge pressure C2

Auto

OFF all fans

Delay able to be set

AL47

Low suction pressure C2

Auto

OFF all comp.

Delay able to be set

AL12

High discharge pressure pressure regulator C2

Set

OFF all com.

AL22

Low suction pressure pressure regulator C2

Auto

OFF all comp.

AL62

Liquid level C2

Manu

Visualization

Delay able to be set

ACC2

Common oil differential C2

Set

Visualization

Delay able to be set

AFC2

Common thermal fans C2

Set

Visualization

ES07

Environment probe broken or disconnected

Auto

Visualization

ES08

External probe broken or disconnected

Auto

Visualization

AH01

Hardware configuration alarm

Auto

Visualization


(*) The low-pressure alarms are not active when the machine is off, while all the others are.