C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
Page 24
-
LP icon:
it is active when the value of suction probe is displayed. If it flashes with alarm
icon switched on, it indicates the intervention of low pressure alarms on suction circuit or suction probe
not-connected.
-
HP icon:
it is active when the value of discharging probe is displayed. If it flashes with
alarm icon switched on, it indicates the intervention of high pressure alarms on discharging circuit or
discharging probe not-connected.
-
Fans icon:
it identifies the fans’ status. If it is switched on, it means that at least one fan is
switched ton, otherwise it remains switched off. If it flashes it means that at least one fan is switched on
in manual function status.
-
Compressors icon: it identifies the compressors’ status. If it is switched on, it means that at least one
compressor is switched on, otherwise it remains switched off. If it flashes it means that at least one
compressor is switched on in manual function status. This display is alternative to the one of 1,2,3,4
icons (parameter PH51).
-
Maintenance icon: it identifies maintenance request. If it is switched on it means that at least one
compressor or one fan has been manually switched on, if it flashes it means that at least one compressor
or one fan has overcome the number of operation hours, otherwise it remains switched off.
-
°C icon:
it identifies the unit of measurement chosen. If it is switched on it indicates the
temperature selection.
-
Bar icon:
it identifies the unit of measurement chosen. If it is switched on it indicates the
pressure selection.
-
1,2,3,4 icons :
they identify the status of the single compressors. If they are switched on, it means
that the compressor is working, if they flash slowly it means that the compressor is in alarm status, if
they flash quickly there is a timing signal in progress for the next switching on or off, Otherwise they
remain switched off. These icons are enabled to parameter PH51 .