beautypg.com

EVCO c-pro nano RACK User Manual

Page 24

background image

C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL

Page 24

-

LP icon:

it is active when the value of suction probe is displayed. If it flashes with alarm

icon switched on, it indicates the intervention of low pressure alarms on suction circuit or suction probe
not-connected.

-

HP icon:

it is active when the value of discharging probe is displayed. If it flashes with

alarm icon switched on, it indicates the intervention of high pressure alarms on discharging circuit or
discharging probe not-connected.

-

Fans icon:

it identifies the fans’ status. If it is switched on, it means that at least one fan is

switched ton, otherwise it remains switched off. If it flashes it means that at least one fan is switched on
in manual function status.

-

Compressors icon: it identifies the compressors’ status. If it is switched on, it means that at least one
compressor is switched on, otherwise it remains switched off. If it flashes it means that at least one
compressor is switched on in manual function status. This display is alternative to the one of 1,2,3,4
icons (parameter PH51).

-

Maintenance icon: it identifies maintenance request. If it is switched on it means that at least one
compressor or one fan has been manually switched on, if it flashes it means that at least one compressor
or one fan has overcome the number of operation hours, otherwise it remains switched off.

-

°C icon:

it identifies the unit of measurement chosen. If it is switched on it indicates the

temperature selection.

-

Bar icon:

it identifies the unit of measurement chosen. If it is switched on it indicates the

pressure selection.

-

1,2,3,4 icons :

they identify the status of the single compressors. If they are switched on, it means

that the compressor is working, if they flash slowly it means that the compressor is in alarm status, if
they flash quickly there is a timing signal in progress for the next switching on or off, Otherwise they
remain switched off. These icons are enabled to parameter PH51 .


This manual is related to the following products: